Digital Acoustics ESBx-110 Dokumentacja Strona 124

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 123
Core Software Operation
ADDvantage-32 PLUS AC to DC Power Converter
3-44
Figure 3-9. Firing Adapter 2-CT Configuration Diagram
24) Return the parameters changed in steps 7 and 8 back to their original values, reset
drive and begin normal, non-AFM drive startup procedure. Continue on to step
25 if there is concern of having the incorrect burden resistor values.
Calculating Burden Resistor Values:
25) For both the 2CT and 3CT configurations (see Figures 1-5 and 1-6), the following
procedure applies to calculating burden resistor values. The value calculated
below corresponds to all three resistors R1 = R2 = R3.
26) Obtain the current rating for the CT. This is usually given as a turns-ratio. This is
equivalent to a ratio of input current to output current (Inpt Amps/Oupt Amps).
Calculate and record the Output Amps of the CT for an input current equal to
300% full load motor current. As an example, for a CT with an 800A/1A rating,
and rated motor armature current of 140A, the output of the CT at 300% motor
current would be:
(1A/800A) * 140A * (300%/100) = 0.525 Amps_Out
Actual CT output current at 300% motor current = _________________ Amps.
Przeglądanie stron 123
1 2 ... 119 120 121 122 123 124 125 126 127 128 129 ... 465 466

Komentarze do niniejszej Instrukcji

Brak uwag